Ohmla

Recommended Wire Size & Voltage Drop for 50A 24V at 25ft (Copper)

View in meters →

Instant Answer

Use 1/0 AWG Copper Wire

Estimated Voltage Drop: 1.27% · Max Recommended Fuse/Breaker: 70A

Adjust the Numbers

Instant Answer

Use 1/0 AWG Copper Wire

Estimated Voltage Drop: 1.27% · Limit: 2%

Recommended AWG1/0 AWG Copper
Circular Mils (CM)105,600
Voltage Lost0.31 V
Percent Drop1.27%
Power Lost15.3 W
Conductor Ampacity (75°C)150 A
Max Recommended Fuse/Breaker70 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 20A 7.85V 32.69% 392.3W 20A
12 AWG 6,530 25A 4.94V 20.58% 246.9W 25A
10 AWG 10,380 35A 3.11V 12.95% 155.3W 35A
8 AWG 16,510 50A 1.95V 8.14% 97.7W 50A
6 AWG 26,240 65A 1.23V 5.12% 61.5W 60A
4 AWG 41,740 85A 0.77V 3.22% 38.6W 70A
2 AWG 66,360 115A 0.49V 2.02% 24.3W 70A
1/0 AWG 105,600 150A 0.31V 1.27% 15.3W 70A
2/0 AWG 133,100 175A 0.24V 1.01% 12.1W 70A
3/0 AWG 167,800 200A 0.19V 0.80% 9.6W 70A
4/0 AWG 211,600 230A 0.15V 0.64% 7.6W 70A

NEC Guidance for 50A Circuits at 24V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 50A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 24V, voltage drop becomes a more significant design constraint because low-voltage DC and solar systems are far more sensitive to line losses.

This calculation assumes a 25ft one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together, though solar and off-grid DC installers typically target a stricter 2% limit to preserve panel output efficiency.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.

Related Calculations