Ohmla

Recommended Wire Size & Voltage Drop for 50A 12V at 100ft (Copper)

View in meters →

Instant Answer

Use 4/0 AWG Copper Wire

Estimated Voltage Drop: 5.08% · Max Recommended Fuse/Breaker: 70A

Adjust the Numbers

Instant Answer

Use 4/0 AWG Copper Wire

Estimated Voltage Drop: 5.08% · Limit: 2%

Recommended AWG4/0 AWG Copper
Circular Mils (CM)211,600
Voltage Lost0.61 V
Percent Drop5.08%
Power Lost30.5 W
Conductor Ampacity (75°C)230 A
Max Recommended Fuse/Breaker70 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 20A 31.39V 261.56% 1569.3W 20A
12 AWG 6,530 25A 19.75V 164.62% 987.7W 25A
10 AWG 10,380 35A 12.43V 103.56% 621.4W 35A
8 AWG 16,510 50A 7.81V 65.11% 390.7W 50A
6 AWG 26,240 65A 4.92V 40.97% 245.8W 60A
4 AWG 41,740 85A 3.09V 25.75% 154.5W 70A
2 AWG 66,360 115A 1.94V 16.20% 97.2W 70A
1/0 AWG 105,600 150A 1.22V 10.18% 61.1W 70A
2/0 AWG 133,100 175A 0.97V 8.08% 48.5W 70A
3/0 AWG 167,800 200A 0.77V 6.41% 38.4W 70A
4/0 AWG 211,600 230A 0.61V 5.08% 30.5W 70A

NEC Guidance for 50A Circuits at 12V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 50A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 12V, voltage drop becomes a more significant design constraint because low-voltage DC and solar systems are far more sensitive to line losses.

This calculation assumes a 100ft one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together, though solar and off-grid DC installers typically target a stricter 2% limit to preserve panel output efficiency.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.

Related Calculations