Ohmla

Recommended Wire Size & Voltage Drop for 50A 120V at 150ft (Copper)

View in meters →

Instant Answer

Use 2 AWG Copper Wire

Estimated Voltage Drop: 2.43% · Max Recommended Fuse/Breaker: 70A

Adjust the Numbers

Instant Answer

Use 2 AWG Copper Wire

Estimated Voltage Drop: 2.43% · Limit: 3%

Recommended AWG2 AWG Copper
Circular Mils (CM)66,360
Voltage Lost2.92 V
Percent Drop2.43%
Power Lost145.8 W
Conductor Ampacity (75°C)115 A
Max Recommended Fuse/Breaker70 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 20A 47.08V 39.23% 2354.0W 20A
12 AWG 6,530 25A 29.63V 24.69% 1481.6W 25A
10 AWG 10,380 35A 18.64V 15.53% 932.1W 35A
8 AWG 16,510 50A 11.72V 9.77% 586.0W 50A
6 AWG 26,240 65A 7.37V 6.15% 368.7W 60A
4 AWG 41,740 85A 4.64V 3.86% 231.8W 70A
2 AWG 66,360 115A 2.92V 2.43% 145.8W 70A
1/0 AWG 105,600 150A 1.83V 1.53% 91.6W 70A
2/0 AWG 133,100 175A 1.45V 1.21% 72.7W 70A
3/0 AWG 167,800 200A 1.15V 0.96% 57.7W 70A
4/0 AWG 211,600 230A 0.91V 0.76% 45.7W 70A

NEC Guidance for 50A Circuits at 120V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 50A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 120V, voltage drop becomes a more significant design constraint over longer conductor runs, since even a small resistive loss represents a larger percentage of the source voltage.

This calculation assumes a 150ft one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.

Related Calculations