Ohmla

Recommended Wire Size & Voltage Drop for 50A 120V at 150ft (Aluminum)

View in meters →

Instant Answer

Use 1/0 AWG Aluminum Wire

Estimated Voltage Drop: 2.51% · Max Recommended Fuse/Breaker: 70A

Adjust the Numbers

Instant Answer

Use 1/0 AWG Aluminum Wire

Estimated Voltage Drop: 2.51% · Limit: 3%

Recommended AWG1/0 AWG Aluminum
Circular Mils (CM)105,600
Voltage Lost3.01 V
Percent Drop2.51%
Power Lost150.6 W
Conductor Ampacity (75°C)120 A
Max Recommended Fuse/Breaker70 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 N/A 77.37V 64.48% 3868.6W 50A
12 AWG 6,530 20A 48.70V 40.58% 2434.9W 20A
10 AWG 10,380 30A 30.64V 25.53% 1531.8W 30A
8 AWG 16,510 40A 19.26V 16.05% 963.1W 40A
6 AWG 26,240 50A 12.12V 10.10% 605.9W 50A
4 AWG 41,740 65A 7.62V 6.35% 380.9W 60A
2 AWG 66,360 90A 4.79V 3.99% 239.6W 70A
1/0 AWG 105,600 120A 3.01V 2.51% 150.6W 70A
2/0 AWG 133,100 135A 2.39V 1.99% 119.5W 70A
3/0 AWG 167,800 155A 1.90V 1.58% 94.8W 70A
4/0 AWG 211,600 180A 1.50V 1.25% 75.1W 70A

NEC Guidance for 50A Circuits at 120V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 50A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 120V, voltage drop becomes a more significant design constraint over longer conductor runs, since even a small resistive loss represents a larger percentage of the source voltage.

This calculation assumes a 150ft one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.

Related Calculations