Ohmla

Recommended Wire Size & Voltage Drop for 15A 120V at 50ft (Copper)

View in meters →

Instant Answer

Use 12 AWG Copper Wire

Estimated Voltage Drop: 2.47% · Max Recommended Fuse/Breaker: 20A

Adjust the Numbers

Instant Answer

Use 12 AWG Copper Wire

Estimated Voltage Drop: 2.47% · Limit: 3%

Recommended AWG12 AWG Copper
Circular Mils (CM)6,530
Voltage Lost2.96 V
Percent Drop2.47%
Power Lost44.4 W
Conductor Ampacity (75°C)25 A
Max Recommended Fuse/Breaker20 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 20A 4.71V 3.92% 70.6W 20A
12 AWG 6,530 25A 2.96V 2.47% 44.4W 20A
10 AWG 10,380 35A 1.86V 1.55% 28.0W 20A
8 AWG 16,510 50A 1.17V 0.98% 17.6W 20A
6 AWG 26,240 65A 0.74V 0.61% 11.1W 20A
4 AWG 41,740 85A 0.46V 0.39% 7.0W 20A
2 AWG 66,360 115A 0.29V 0.24% 4.4W 20A
1/0 AWG 105,600 150A 0.18V 0.15% 2.7W 20A
2/0 AWG 133,100 175A 0.15V 0.12% 2.2W 20A
3/0 AWG 167,800 200A 0.12V 0.10% 1.7W 20A
4/0 AWG 211,600 230A 0.09V 0.08% 1.4W 20A

NEC Guidance for 15A Circuits at 120V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 15A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 120V, voltage drop becomes a more significant design constraint over longer conductor runs, since even a small resistive loss represents a larger percentage of the source voltage.

This calculation assumes a 50ft one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.

Related Calculations