Ohmla

Recommended Wire Size & Voltage Drop for 15A 12V at 100ft (Aluminum)

View in meters →

Instant Answer

Use 4/0 AWG Aluminum Wire

Estimated Voltage Drop: 2.50% · Max Recommended Fuse/Breaker: 20A

Adjust the Numbers

Instant Answer

Use 4/0 AWG Aluminum Wire

Estimated Voltage Drop: 2.50% · Limit: 2%

Recommended AWG4/0 AWG Aluminum
Circular Mils (CM)211,600
Voltage Lost0.30 V
Percent Drop2.50%
Power Lost4.5 W
Conductor Ampacity (75°C)180 A
Max Recommended Fuse/Breaker20 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 N/A 15.47V 128.95% 232.1W 15A
12 AWG 6,530 20A 9.74V 81.16% 146.1W 20A
10 AWG 10,380 30A 6.13V 51.06% 91.9W 20A
8 AWG 16,510 40A 3.85V 32.10% 57.8W 20A
6 AWG 26,240 50A 2.42V 20.20% 36.4W 20A
4 AWG 41,740 65A 1.52V 12.70% 22.9W 20A
2 AWG 66,360 90A 0.96V 7.99% 14.4W 20A
1/0 AWG 105,600 120A 0.60V 5.02% 9.0W 20A
2/0 AWG 133,100 135A 0.48V 3.98% 7.2W 20A
3/0 AWG 167,800 155A 0.38V 3.16% 5.7W 20A
4/0 AWG 211,600 180A 0.30V 2.50% 4.5W 20A

NEC Guidance for 15A Circuits at 12V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 15A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 12V, voltage drop becomes a more significant design constraint because low-voltage DC and solar systems are far more sensitive to line losses.

This calculation assumes a 100ft one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together, though solar and off-grid DC installers typically target a stricter 2% limit to preserve panel output efficiency.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.