Recommended Wire Size & Voltage Drop for 15A 120V at 300ft (Aluminum)

View in meters →

Instant Answer

Use 2 AWG Aluminum Wire

Estimated Voltage Drop: 2.40% · Max Recommended Fuse/Breaker: 20A

Adjust the Numbers

Instant Answer

Use 2 AWG Aluminum Wire

Estimated Voltage Drop: 2.40% · Limit: 3%

Recommended AWG2 AWG Aluminum
Circular Mils (CM)66,360
Voltage Lost2.88 V
Percent Drop2.40%
Power Lost43.1 W
Conductor Ampacity (75°C)90 A
Max Recommended Fuse/Breaker20 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 N/A 46.42V 38.69% 696.4W 15A
12 AWG 6,530 20A 29.22V 24.35% 438.3W 20A
10 AWG 10,380 30A 18.38V 15.32% 275.7W 20A
8 AWG 16,510 40A 11.56V 9.63% 173.3W 20A
6 AWG 26,240 50A 7.27V 6.06% 109.1W 20A
4 AWG 41,740 65A 4.57V 3.81% 68.6W 20A
2 AWG 66,360 90A 2.88V 2.40% 43.1W 20A
1/0 AWG 105,600 120A 1.81V 1.51% 27.1W 20A
2/0 AWG 133,100 135A 1.43V 1.19% 21.5W 20A
3/0 AWG 167,800 155A 1.14V 0.95% 17.1W 20A
4/0 AWG 211,600 180A 0.90V 0.75% 13.5W 20A

NEC Guidance for 15A Circuits at 120V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 15A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 120V, voltage drop becomes a more significant design constraint over longer conductor runs, since even a small resistive loss represents a larger percentage of the source voltage.

This calculation assumes a 300ft one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.