Recommended Wire Size & Voltage Drop for 30A 24V at 25ft (Aluminum)

View in meters →

Instant Answer

Use 2 AWG Aluminum Wire

Estimated Voltage Drop: 2.00% · Max Recommended Fuse/Breaker: 40A

Adjust the Numbers

Instant Answer

Use 2 AWG Aluminum Wire

Estimated Voltage Drop: 2.00% · Limit: 2%

Recommended AWG2 AWG Aluminum
Circular Mils (CM)66,360
Voltage Lost0.48 V
Percent Drop2.00%
Power Lost14.4 W
Conductor Ampacity (75°C)90 A
Max Recommended Fuse/Breaker40 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 N/A 7.74V 32.24% 232.1W 30A
12 AWG 6,530 20A 4.87V 20.29% 146.1W 20A
10 AWG 10,380 30A 3.06V 12.76% 91.9W 30A
8 AWG 16,510 40A 1.93V 8.03% 57.8W 40A
6 AWG 26,240 50A 1.21V 5.05% 36.4W 40A
4 AWG 41,740 65A 0.76V 3.17% 22.9W 40A
2 AWG 66,360 90A 0.48V 2.00% 14.4W 40A
1/0 AWG 105,600 120A 0.30V 1.25% 9.0W 40A
2/0 AWG 133,100 135A 0.24V 1.00% 7.2W 40A
3/0 AWG 167,800 155A 0.19V 0.79% 5.7W 40A
4/0 AWG 211,600 180A 0.15V 0.63% 4.5W 40A

NEC Guidance for 30A Circuits at 24V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 30A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 24V, voltage drop becomes a more significant design constraint because low-voltage DC and solar systems are far more sensitive to line losses.

This calculation assumes a 25ft one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together, though solar and off-grid DC installers typically target a stricter 2% limit to preserve panel output efficiency.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.