Ohmla

Recommended Wire Size & Voltage Drop for 30A 12V at 100ft (Copper)

View in meters →

Instant Answer

Use 4/0 AWG Copper Wire

Estimated Voltage Drop: 3.05% · Max Recommended Fuse/Breaker: 40A

Adjust the Numbers

Instant Answer

Use 4/0 AWG Copper Wire

Estimated Voltage Drop: 3.05% · Limit: 2%

Recommended AWG4/0 AWG Copper
Circular Mils (CM)211,600
Voltage Lost0.37 V
Percent Drop3.05%
Power Lost11.0 W
Conductor Ampacity (75°C)230 A
Max Recommended Fuse/Breaker40 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 20A 18.83V 156.93% 565.0W 20A
12 AWG 6,530 25A 11.85V 98.77% 355.6W 25A
10 AWG 10,380 35A 7.46V 62.14% 223.7W 35A
8 AWG 16,510 50A 4.69V 39.07% 140.6W 40A
6 AWG 26,240 65A 2.95V 24.58% 88.5W 40A
4 AWG 41,740 85A 1.85V 15.45% 55.6W 40A
2 AWG 66,360 115A 1.17V 9.72% 35.0W 40A
1/0 AWG 105,600 150A 0.73V 6.11% 22.0W 40A
2/0 AWG 133,100 175A 0.58V 4.85% 17.4W 40A
3/0 AWG 167,800 200A 0.46V 3.84% 13.8W 40A
4/0 AWG 211,600 230A 0.37V 3.05% 11.0W 40A

NEC Guidance for 30A Circuits at 12V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 30A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 12V, voltage drop becomes a more significant design constraint because low-voltage DC and solar systems are far more sensitive to line losses.

This calculation assumes a 100ft one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together, though solar and off-grid DC installers typically target a stricter 2% limit to preserve panel output efficiency.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.

Related Calculations