Recommended Wire Size & Voltage Drop for 30A 120V at 300ft (Copper)
View in meters →Instant Answer
Use 2 AWG Copper Wire
Estimated Voltage Drop: 2.92% · Max Recommended Fuse/Breaker: 40A
Ohmla — Wire Sizing Spec Sheet
Generated July 27, 2026 · ohmla.com
| Load Current | 30 A |
| Source Voltage | 120 V |
| One-Way Distance | 300 ft |
| Conductor Material | Copper |
| Recommended AWG | 2 AWG |
| Circular Mils | 66,360 |
| Voltage Drop | 3.50 V |
| Percent Drop | 2.92% (limit 3%) |
| Power Lost | 105.0 W |
| Conductor Ampacity (75°C) | 115 A |
| Max Recommended Fuse/Breaker | 40 A |
This spec sheet is an engineering estimate based on NEC Table 310.16 (75°C ampacity) and NEC Chapter 9, Table 8 (circular mils), assuming a 30°C ambient and standard conductor bundling. It is provided for reference only and does not replace a code-compliant load calculation or inspection performed by a licensed electrician. Verify against the current NEC/CEC edition adopted in your jurisdiction.
Adjust the Numbers
Instant Answer
Use 2 AWG Copper Wire
Estimated Voltage Drop: 2.92% · Limit: 3%
| Recommended AWG | 2 AWG Copper |
| Circular Mils (CM) | 66,360 |
| Voltage Lost | 3.50 V |
| Percent Drop | 2.92% |
| Power Lost | 105.0 W |
| Conductor Ampacity (75°C) | 115 A |
| Max Recommended Fuse/Breaker | 40 A |
Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.
Full Technical Spec Table
| AWG | Circular Mils | Ampacity (75°C) | Voltage Lost | % Drop | Power Lost | Max Fuse |
|---|---|---|---|---|---|---|
| 14 AWG | 4,110 | 20A | 56.50V | 47.08% | 1694.9W | 20A |
| 12 AWG | 6,530 | 25A | 35.56V | 29.63% | 1066.8W | 25A |
| 10 AWG | 10,380 | 35A | 22.37V | 18.64% | 671.1W | 35A |
| 8 AWG | 16,510 | 50A | 14.06V | 11.72% | 421.9W | 40A |
| 6 AWG | 26,240 | 65A | 8.85V | 7.37% | 265.5W | 40A |
| 4 AWG | 41,740 | 85A | 5.56V | 4.64% | 166.9W | 40A |
| 2 AWG | 66,360 | 115A | 3.50V | 2.92% | 105.0W | 40A |
| 1/0 AWG | 105,600 | 150A | 2.20V | 1.83% | 66.0W | 40A |
| 2/0 AWG | 133,100 | 175A | 1.74V | 1.45% | 52.3W | 40A |
| 3/0 AWG | 167,800 | 200A | 1.38V | 1.15% | 41.5W | 40A |
| 4/0 AWG | 211,600 | 230A | 1.10V | 0.91% | 32.9W | 40A |
NEC Guidance for 30A Circuits at 120V
Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 30A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 120V, voltage drop becomes a more significant design constraint over longer conductor runs, since even a small resistive loss represents a larger percentage of the source voltage.
This calculation assumes a 300ft one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together.
Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):
- 26-30°C (78-86°F): multiply ampacity by 1
- 31-35°C (87-95°F): multiply ampacity by 0.94
- 36-40°C (96-104°F): multiply ampacity by 0.88
- 41-45°C (105-113°F): multiply ampacity by 0.82
- 46-50°C (114-122°F): multiply ampacity by 0.75
- 51-55°C (123-131°F): multiply ampacity by 0.67
For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.