Recommended Wire Size & Voltage Drop for 50A 480V at 91m (Copper)

View in feet →

Instant Answer

Use 4 AWG Copper Wire

Estimated Voltage Drop: 1.93% · Max Recommended Fuse/Breaker: 70A

Adjust the Numbers

Instant Answer

Use 4 AWG Copper Wire

Estimated Voltage Drop: 1.93% · Limit: 3%

Recommended AWG4 AWG Copper
Circular Mils (CM)41,740
Voltage Lost9.27 V
Percent Drop1.93%
Power Lost463.6 W
Conductor Ampacity (75°C)85 A
Max Recommended Fuse/Breaker70 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 20A 94.16V 19.62% 4708.0W 20A
12 AWG 6,530 25A 59.26V 12.35% 2963.2W 25A
10 AWG 10,380 35A 37.28V 7.77% 1864.2W 35A
8 AWG 16,510 50A 23.44V 4.88% 1172.0W 50A
6 AWG 26,240 65A 14.75V 3.07% 737.4W 60A
4 AWG 41,740 85A 9.27V 1.93% 463.6W 70A
2 AWG 66,360 115A 5.83V 1.21% 291.6W 70A
1/0 AWG 105,600 150A 3.66V 0.76% 183.2W 70A
2/0 AWG 133,100 175A 2.91V 0.61% 145.4W 70A
3/0 AWG 167,800 200A 2.31V 0.48% 115.3W 70A
4/0 AWG 211,600 230A 1.83V 0.38% 91.4W 70A

NEC Guidance for 50A Circuits at 480V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 50A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 480V, voltage drop becomes a more significant design constraint over longer conductor runs, since even a small resistive loss represents a larger percentage of the source voltage.

This calculation assumes a 91m one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.