Ohmla

Recommended Wire Size & Voltage Drop for 50A 240V at 30m (Aluminum)

View in feet →

Instant Answer

Use 4 AWG Aluminum Wire

Estimated Voltage Drop: 2.12% · Max Recommended Fuse/Breaker: 60A

Adjust the Numbers

Instant Answer

Use 4 AWG Aluminum Wire

Estimated Voltage Drop: 2.12% · Limit: 3%

Recommended AWG4 AWG Aluminum
Circular Mils (CM)41,740
Voltage Lost5.08 V
Percent Drop2.12%
Power Lost254.0 W
Conductor Ampacity (75°C)65 A
Max Recommended Fuse/Breaker60 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 N/A 51.58V 21.49% 2579.1W 50A
12 AWG 6,530 20A 32.47V 13.53% 1623.3W 20A
10 AWG 10,380 30A 20.42V 8.51% 1021.2W 30A
8 AWG 16,510 40A 12.84V 5.35% 642.0W 40A
6 AWG 26,240 50A 8.08V 3.37% 404.0W 50A
4 AWG 41,740 65A 5.08V 2.12% 254.0W 60A
2 AWG 66,360 90A 3.19V 1.33% 159.7W 70A
1/0 AWG 105,600 120A 2.01V 0.84% 100.4W 70A
2/0 AWG 133,100 135A 1.59V 0.66% 79.6W 70A
3/0 AWG 167,800 155A 1.26V 0.53% 63.2W 70A
4/0 AWG 211,600 180A 1.00V 0.42% 50.1W 70A

NEC Guidance for 50A Circuits at 240V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 50A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 240V, voltage drop becomes a more significant design constraint over longer conductor runs, since even a small resistive loss represents a larger percentage of the source voltage.

This calculation assumes a 30m one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.

Related Calculations