Recommended Wire Size & Voltage Drop for 30A 24V at 46m (Copper)

View in feet →

Instant Answer

Use 4/0 AWG Copper Wire

Estimated Voltage Drop: 2.29% · Max Recommended Fuse/Breaker: 40A

Adjust the Numbers

Instant Answer

Use 4/0 AWG Copper Wire

Estimated Voltage Drop: 2.29% · Limit: 2%

Recommended AWG4/0 AWG Copper
Circular Mils (CM)211,600
Voltage Lost0.55 V
Percent Drop2.29%
Power Lost16.5 W
Conductor Ampacity (75°C)230 A
Max Recommended Fuse/Breaker40 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 20A 28.25V 117.70% 847.4W 20A
12 AWG 6,530 25A 17.78V 74.08% 533.4W 25A
10 AWG 10,380 35A 11.18V 46.60% 335.5W 35A
8 AWG 16,510 50A 7.03V 29.30% 211.0W 40A
6 AWG 26,240 65A 4.42V 18.44% 132.7W 40A
4 AWG 41,740 85A 2.78V 11.59% 83.4W 40A
2 AWG 66,360 115A 1.75V 7.29% 52.5W 40A
1/0 AWG 105,600 150A 1.10V 4.58% 33.0W 40A
2/0 AWG 133,100 175A 0.87V 3.63% 26.2W 40A
3/0 AWG 167,800 200A 0.69V 2.88% 20.8W 40A
4/0 AWG 211,600 230A 0.55V 2.29% 16.5W 40A

NEC Guidance for 30A Circuits at 24V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 30A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 24V, voltage drop becomes a more significant design constraint because low-voltage DC and solar systems are far more sensitive to line losses.

This calculation assumes a 46m one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together, though solar and off-grid DC installers typically target a stricter 2% limit to preserve panel output efficiency.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.