Recommended Wire Size & Voltage Drop for 200A 480V at 200ft (Aluminum)

View in meters →

Instant Answer

Use 4/0 AWG Aluminum Wire

Estimated Voltage Drop: 1.67% · Max Recommended Fuse/Breaker: 175A

Adjust the Numbers

Instant Answer

Use 4/0 AWG Aluminum Wire

Estimated Voltage Drop: 1.67% · Limit: 3%

Recommended AWG4/0 AWG Aluminum
Circular Mils (CM)211,600
Voltage Lost8.02 V
Percent Drop1.67%
Power Lost1603.0 W
Conductor Ampacity (75°C)180 A
Max Recommended Fuse/Breaker175 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 N/A 412.65V 85.97% 82530.4W 200A
12 AWG 6,530 20A 259.72V 54.11% 51944.9W 20A
10 AWG 10,380 30A 163.39V 34.04% 32678.2W 30A
8 AWG 16,510 40A 102.73V 21.40% 20545.1W 40A
6 AWG 26,240 50A 64.63V 13.47% 12926.8W 50A
4 AWG 41,740 65A 40.63V 8.47% 8126.5W 60A
2 AWG 66,360 90A 25.56V 5.32% 5111.5W 90A
1/0 AWG 105,600 120A 16.06V 3.35% 3212.1W 110A
2/0 AWG 133,100 135A 12.74V 2.65% 2548.5W 125A
3/0 AWG 167,800 155A 10.11V 2.11% 2021.5W 150A
4/0 AWG 211,600 180A 8.02V 1.67% 1603.0W 175A

NEC Guidance for 200A Circuits at 480V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 200A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 480V, voltage drop becomes a more significant design constraint over longer conductor runs, since even a small resistive loss represents a larger percentage of the source voltage.

This calculation assumes a 200ft one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.