Ohmla

Recommended Wire Size & Voltage Drop for 200A 240V at 8m (Aluminum)

View in feet →

Instant Answer

Use 4/0 AWG Aluminum Wire

Estimated Voltage Drop: 0.42% · Max Recommended Fuse/Breaker: 175A

Adjust the Numbers

Instant Answer

Use 4/0 AWG Aluminum Wire

Estimated Voltage Drop: 0.42% · Limit: 3%

Recommended AWG4/0 AWG Aluminum
Circular Mils (CM)211,600
Voltage Lost1.00 V
Percent Drop0.42%
Power Lost200.4 W
Conductor Ampacity (75°C)180 A
Max Recommended Fuse/Breaker175 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 N/A 51.58V 21.49% 10316.3W 200A
12 AWG 6,530 20A 32.47V 13.53% 6493.1W 20A
10 AWG 10,380 30A 20.42V 8.51% 4084.8W 30A
8 AWG 16,510 40A 12.84V 5.35% 2568.1W 40A
6 AWG 26,240 50A 8.08V 3.37% 1615.9W 50A
4 AWG 41,740 65A 5.08V 2.12% 1015.8W 60A
2 AWG 66,360 90A 3.19V 1.33% 638.9W 90A
1/0 AWG 105,600 120A 2.01V 0.84% 401.5W 110A
2/0 AWG 133,100 135A 1.59V 0.66% 318.6W 125A
3/0 AWG 167,800 155A 1.26V 0.53% 252.7W 150A
4/0 AWG 211,600 180A 1.00V 0.42% 200.4W 175A

NEC Guidance for 200A Circuits at 240V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 200A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 240V, voltage drop becomes a more significant design constraint over longer conductor runs, since even a small resistive loss represents a larger percentage of the source voltage.

This calculation assumes a 8m one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.

Related Calculations