Ohmla

Recommended Wire Size & Voltage Drop for 200A 240V at 300ft (Aluminum)

View in meters →

Instant Answer

Use 4/0 AWG Aluminum Wire

Estimated Voltage Drop: 5.01% · Max Recommended Fuse/Breaker: 175A

Adjust the Numbers

Instant Answer

Use 4/0 AWG Aluminum Wire

Estimated Voltage Drop: 5.01% · Limit: 3%

Recommended AWG4/0 AWG Aluminum
Circular Mils (CM)211,600
Voltage Lost12.02 V
Percent Drop5.01%
Power Lost2404.5 W
Conductor Ampacity (75°C)180 A
Max Recommended Fuse/Breaker175 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 N/A 618.98V 257.91% 123795.6W 200A
12 AWG 6,530 20A 389.59V 162.33% 77917.3W 20A
10 AWG 10,380 30A 245.09V 102.12% 49017.3W 30A
8 AWG 16,510 40A 154.09V 64.20% 30817.7W 40A
6 AWG 26,240 50A 96.95V 40.40% 19390.2W 50A
4 AWG 41,740 65A 60.95V 25.40% 12189.7W 60A
2 AWG 66,360 90A 38.34V 15.97% 7667.3W 90A
1/0 AWG 105,600 120A 24.09V 10.04% 4818.2W 110A
2/0 AWG 133,100 135A 19.11V 7.96% 3822.7W 125A
3/0 AWG 167,800 155A 15.16V 6.32% 3032.2W 150A
4/0 AWG 211,600 180A 12.02V 5.01% 2404.5W 175A

NEC Guidance for 200A Circuits at 240V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 200A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 240V, voltage drop becomes a more significant design constraint over longer conductor runs, since even a small resistive loss represents a larger percentage of the source voltage.

This calculation assumes a 300ft one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.

Related Calculations