Ohmla

Recommended Wire Size & Voltage Drop for 20A 240V at 300ft (Aluminum)

View in meters →

Instant Answer

Use 4 AWG Aluminum Wire

Estimated Voltage Drop: 2.54% · Max Recommended Fuse/Breaker: 25A

Adjust the Numbers

Instant Answer

Use 4 AWG Aluminum Wire

Estimated Voltage Drop: 2.54% · Limit: 3%

Recommended AWG4 AWG Aluminum
Circular Mils (CM)41,740
Voltage Lost6.09 V
Percent Drop2.54%
Power Lost121.9 W
Conductor Ampacity (75°C)65 A
Max Recommended Fuse/Breaker25 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 N/A 61.90V 25.79% 1238.0W 20A
12 AWG 6,530 20A 38.96V 16.23% 779.2W 20A
10 AWG 10,380 30A 24.51V 10.21% 490.2W 25A
8 AWG 16,510 40A 15.41V 6.42% 308.2W 25A
6 AWG 26,240 50A 9.70V 4.04% 193.9W 25A
4 AWG 41,740 65A 6.09V 2.54% 121.9W 25A
2 AWG 66,360 90A 3.83V 1.60% 76.7W 25A
1/0 AWG 105,600 120A 2.41V 1.00% 48.2W 25A
2/0 AWG 133,100 135A 1.91V 0.80% 38.2W 25A
3/0 AWG 167,800 155A 1.52V 0.63% 30.3W 25A
4/0 AWG 211,600 180A 1.20V 0.50% 24.0W 25A

NEC Guidance for 20A Circuits at 240V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 20A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 240V, voltage drop becomes a more significant design constraint over longer conductor runs, since even a small resistive loss represents a larger percentage of the source voltage.

This calculation assumes a 300ft one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.

Related Calculations