Ohmla

Recommended Wire Size & Voltage Drop for 20A 120V at 30m (Copper)

View in feet →

Instant Answer

Use 8 AWG Copper Wire

Estimated Voltage Drop: 2.60% · Max Recommended Fuse/Breaker: 25A

Adjust the Numbers

Instant Answer

Use 8 AWG Copper Wire

Estimated Voltage Drop: 2.60% · Limit: 3%

Recommended AWG8 AWG Copper
Circular Mils (CM)16,510
Voltage Lost3.13 V
Percent Drop2.60%
Power Lost62.5 W
Conductor Ampacity (75°C)50 A
Max Recommended Fuse/Breaker25 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 20A 12.55V 10.46% 251.1W 20A
12 AWG 6,530 25A 7.90V 6.58% 158.0W 25A
10 AWG 10,380 35A 4.97V 4.14% 99.4W 25A
8 AWG 16,510 50A 3.13V 2.60% 62.5W 25A
6 AWG 26,240 65A 1.97V 1.64% 39.3W 25A
4 AWG 41,740 85A 1.24V 1.03% 24.7W 25A
2 AWG 66,360 115A 0.78V 0.65% 15.6W 25A
1/0 AWG 105,600 150A 0.49V 0.41% 9.8W 25A
2/0 AWG 133,100 175A 0.39V 0.32% 7.8W 25A
3/0 AWG 167,800 200A 0.31V 0.26% 6.2W 25A
4/0 AWG 211,600 230A 0.24V 0.20% 4.9W 25A

NEC Guidance for 20A Circuits at 120V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 20A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 120V, voltage drop becomes a more significant design constraint over longer conductor runs, since even a small resistive loss represents a larger percentage of the source voltage.

This calculation assumes a 30m one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.

Related Calculations