Recommended Wire Size & Voltage Drop for 20A 120V at 200ft (Copper)

View in meters →

Instant Answer

Use 4 AWG Copper Wire

Estimated Voltage Drop: 2.06% · Max Recommended Fuse/Breaker: 25A

Adjust the Numbers

Instant Answer

Use 4 AWG Copper Wire

Estimated Voltage Drop: 2.06% · Limit: 3%

Recommended AWG4 AWG Copper
Circular Mils (CM)41,740
Voltage Lost2.47 V
Percent Drop2.06%
Power Lost49.4 W
Conductor Ampacity (75°C)85 A
Max Recommended Fuse/Breaker25 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 20A 25.11V 20.92% 502.2W 20A
12 AWG 6,530 25A 15.80V 13.17% 316.1W 25A
10 AWG 10,380 35A 9.94V 8.29% 198.8W 25A
8 AWG 16,510 50A 6.25V 5.21% 125.0W 25A
6 AWG 26,240 65A 3.93V 3.28% 78.7W 25A
4 AWG 41,740 85A 2.47V 2.06% 49.4W 25A
2 AWG 66,360 115A 1.56V 1.30% 31.1W 25A
1/0 AWG 105,600 150A 0.98V 0.81% 19.5W 25A
2/0 AWG 133,100 175A 0.78V 0.65% 15.5W 25A
3/0 AWG 167,800 200A 0.62V 0.51% 12.3W 25A
4/0 AWG 211,600 230A 0.49V 0.41% 9.8W 25A

NEC Guidance for 20A Circuits at 120V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 20A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 120V, voltage drop becomes a more significant design constraint over longer conductor runs, since even a small resistive loss represents a larger percentage of the source voltage.

This calculation assumes a 200ft one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.