Ohmla

Recommended Wire Size & Voltage Drop for 15A 24V at 46m (Aluminum)

View in feet →

Instant Answer

Use 4/0 AWG Aluminum Wire

Estimated Voltage Drop: 1.88% · Max Recommended Fuse/Breaker: 20A

Adjust the Numbers

Instant Answer

Use 4/0 AWG Aluminum Wire

Estimated Voltage Drop: 1.88% · Limit: 2%

Recommended AWG4/0 AWG Aluminum
Circular Mils (CM)211,600
Voltage Lost0.45 V
Percent Drop1.88%
Power Lost6.8 W
Conductor Ampacity (75°C)180 A
Max Recommended Fuse/Breaker20 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 N/A 23.21V 96.72% 348.2W 15A
12 AWG 6,530 20A 14.61V 60.87% 219.1W 20A
10 AWG 10,380 30A 9.19V 38.29% 137.9W 20A
8 AWG 16,510 40A 5.78V 24.08% 86.7W 20A
6 AWG 26,240 50A 3.64V 15.15% 54.5W 20A
4 AWG 41,740 65A 2.29V 9.52% 34.3W 20A
2 AWG 66,360 90A 1.44V 5.99% 21.6W 20A
1/0 AWG 105,600 120A 0.90V 3.76% 13.6W 20A
2/0 AWG 133,100 135A 0.72V 2.99% 10.8W 20A
3/0 AWG 167,800 155A 0.57V 2.37% 8.5W 20A
4/0 AWG 211,600 180A 0.45V 1.88% 6.8W 20A

NEC Guidance for 15A Circuits at 24V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 15A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 24V, voltage drop becomes a more significant design constraint because low-voltage DC and solar systems are far more sensitive to line losses.

This calculation assumes a 46m one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together, though solar and off-grid DC installers typically target a stricter 2% limit to preserve panel output efficiency.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.

Related Calculations