Recommended Wire Size & Voltage Drop for 15A 240V at 46m (Copper)

View in feet →

Instant Answer

Use 10 AWG Copper Wire

Estimated Voltage Drop: 2.33% · Max Recommended Fuse/Breaker: 20A

Adjust the Numbers

Instant Answer

Use 10 AWG Copper Wire

Estimated Voltage Drop: 2.33% · Limit: 3%

Recommended AWG10 AWG Copper
Circular Mils (CM)10,380
Voltage Lost5.59 V
Percent Drop2.33%
Power Lost83.9 W
Conductor Ampacity (75°C)35 A
Max Recommended Fuse/Breaker20 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 20A 14.12V 5.89% 211.9W 20A
12 AWG 6,530 25A 8.89V 3.70% 133.3W 20A
10 AWG 10,380 35A 5.59V 2.33% 83.9W 20A
8 AWG 16,510 50A 3.52V 1.47% 52.7W 20A
6 AWG 26,240 65A 2.21V 0.92% 33.2W 20A
4 AWG 41,740 85A 1.39V 0.58% 20.9W 20A
2 AWG 66,360 115A 0.87V 0.36% 13.1W 20A
1/0 AWG 105,600 150A 0.55V 0.23% 8.2W 20A
2/0 AWG 133,100 175A 0.44V 0.18% 6.5W 20A
3/0 AWG 167,800 200A 0.35V 0.14% 5.2W 20A
4/0 AWG 211,600 230A 0.27V 0.11% 4.1W 20A

NEC Guidance for 15A Circuits at 240V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 15A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 240V, voltage drop becomes a more significant design constraint over longer conductor runs, since even a small resistive loss represents a larger percentage of the source voltage.

This calculation assumes a 46m one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.