Recommended Wire Size & Voltage Drop for 100A 480V at 8m (Copper)

View in feet →

Instant Answer

Use 2 AWG Copper Wire

Estimated Voltage Drop: 0.20% · Max Recommended Fuse/Breaker: 110A

Adjust the Numbers

Instant Answer

Use 2 AWG Copper Wire

Estimated Voltage Drop: 0.20% · Limit: 3%

Recommended AWG2 AWG Copper
Circular Mils (CM)66,360
Voltage Lost0.97 V
Percent Drop0.20%
Power Lost97.2 W
Conductor Ampacity (75°C)115 A
Max Recommended Fuse/Breaker110 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 20A 15.69V 3.27% 1569.3W 20A
12 AWG 6,530 25A 9.88V 2.06% 987.7W 25A
10 AWG 10,380 35A 6.21V 1.29% 621.4W 35A
8 AWG 16,510 50A 3.91V 0.81% 390.7W 50A
6 AWG 26,240 65A 2.46V 0.51% 245.8W 60A
4 AWG 41,740 85A 1.55V 0.32% 154.5W 80A
2 AWG 66,360 115A 0.97V 0.20% 97.2W 110A
1/0 AWG 105,600 150A 0.61V 0.13% 61.1W 125A
2/0 AWG 133,100 175A 0.48V 0.10% 48.5W 125A
3/0 AWG 167,800 200A 0.38V 0.08% 38.4W 125A
4/0 AWG 211,600 230A 0.30V 0.06% 30.5W 125A

NEC Guidance for 100A Circuits at 480V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 100A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 480V, voltage drop becomes a more significant design constraint over longer conductor runs, since even a small resistive loss represents a larger percentage of the source voltage.

This calculation assumes a 8m one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.