Recommended Wire Size & Voltage Drop for 100A 480V at 46m (Aluminum)

View in feet →

Instant Answer

Use 1/0 AWG Aluminum Wire

Estimated Voltage Drop: 1.25% · Max Recommended Fuse/Breaker: 110A

Adjust the Numbers

Instant Answer

Use 1/0 AWG Aluminum Wire

Estimated Voltage Drop: 1.25% · Limit: 3%

Recommended AWG1/0 AWG Aluminum
Circular Mils (CM)105,600
Voltage Lost6.02 V
Percent Drop1.25%
Power Lost602.3 W
Conductor Ampacity (75°C)120 A
Max Recommended Fuse/Breaker110 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 N/A 154.74V 32.24% 15474.5W 100A
12 AWG 6,530 20A 97.40V 20.29% 9739.7W 20A
10 AWG 10,380 30A 61.27V 12.76% 6127.2W 30A
8 AWG 16,510 40A 38.52V 8.03% 3852.2W 40A
6 AWG 26,240 50A 24.24V 5.05% 2423.8W 50A
4 AWG 41,740 65A 15.24V 3.17% 1523.7W 60A
2 AWG 66,360 90A 9.58V 2.00% 958.4W 90A
1/0 AWG 105,600 120A 6.02V 1.25% 602.3W 110A
2/0 AWG 133,100 135A 4.78V 1.00% 477.8W 125A
3/0 AWG 167,800 155A 3.79V 0.79% 379.0W 125A
4/0 AWG 211,600 180A 3.01V 0.63% 300.6W 125A

NEC Guidance for 100A Circuits at 480V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 100A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 480V, voltage drop becomes a more significant design constraint over longer conductor runs, since even a small resistive loss represents a larger percentage of the source voltage.

This calculation assumes a 46m one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.