Recommended Wire Size & Voltage Drop for 100A 480V at 200ft (Aluminum)

View in meters →

Instant Answer

Use 1/0 AWG Aluminum Wire

Estimated Voltage Drop: 1.67% · Max Recommended Fuse/Breaker: 110A

Adjust the Numbers

Instant Answer

Use 1/0 AWG Aluminum Wire

Estimated Voltage Drop: 1.67% · Limit: 3%

Recommended AWG1/0 AWG Aluminum
Circular Mils (CM)105,600
Voltage Lost8.03 V
Percent Drop1.67%
Power Lost803.0 W
Conductor Ampacity (75°C)120 A
Max Recommended Fuse/Breaker110 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 N/A 206.33V 42.98% 20632.6W 100A
12 AWG 6,530 20A 129.86V 27.05% 12986.2W 20A
10 AWG 10,380 30A 81.70V 17.02% 8169.6W 30A
8 AWG 16,510 40A 51.36V 10.70% 5136.3W 40A
6 AWG 26,240 50A 32.32V 6.73% 3231.7W 50A
4 AWG 41,740 65A 20.32V 4.23% 2031.6W 60A
2 AWG 66,360 90A 12.78V 2.66% 1277.9W 90A
1/0 AWG 105,600 120A 8.03V 1.67% 803.0W 110A
2/0 AWG 133,100 135A 6.37V 1.33% 637.1W 125A
3/0 AWG 167,800 155A 5.05V 1.05% 505.4W 125A
4/0 AWG 211,600 180A 4.01V 0.83% 400.8W 125A

NEC Guidance for 100A Circuits at 480V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 100A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 480V, voltage drop becomes a more significant design constraint over longer conductor runs, since even a small resistive loss represents a larger percentage of the source voltage.

This calculation assumes a 200ft one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.