Ohmla

Recommended Wire Size & Voltage Drop for 100A 24V at 50ft (Aluminum)

View in meters →

Instant Answer

Use 4/0 AWG Aluminum Wire

Estimated Voltage Drop: 4.17% · Max Recommended Fuse/Breaker: 125A

Adjust the Numbers

Instant Answer

Use 4/0 AWG Aluminum Wire

Estimated Voltage Drop: 4.17% · Limit: 2%

Recommended AWG4/0 AWG Aluminum
Circular Mils (CM)211,600
Voltage Lost1.00 V
Percent Drop4.17%
Power Lost100.2 W
Conductor Ampacity (75°C)180 A
Max Recommended Fuse/Breaker125 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 N/A 51.58V 214.92% 5158.2W 100A
12 AWG 6,530 20A 32.47V 135.27% 3246.6W 20A
10 AWG 10,380 30A 20.42V 85.10% 2042.4W 30A
8 AWG 16,510 40A 12.84V 53.50% 1284.1W 40A
6 AWG 26,240 50A 8.08V 33.66% 807.9W 50A
4 AWG 41,740 65A 5.08V 21.16% 507.9W 60A
2 AWG 66,360 90A 3.19V 13.31% 319.5W 90A
1/0 AWG 105,600 120A 2.01V 8.36% 200.8W 110A
2/0 AWG 133,100 135A 1.59V 6.64% 159.3W 125A
3/0 AWG 167,800 155A 1.26V 5.26% 126.3W 125A
4/0 AWG 211,600 180A 1.00V 4.17% 100.2W 125A

NEC Guidance for 100A Circuits at 24V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 100A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 24V, voltage drop becomes a more significant design constraint because low-voltage DC and solar systems are far more sensitive to line losses.

This calculation assumes a 50ft one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together, though solar and off-grid DC installers typically target a stricter 2% limit to preserve panel output efficiency.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.

Related Calculations