Recommended Wire Size & Voltage Drop for 100A 12V at 46m (Copper)

View in feet →

Instant Answer

Use 4/0 AWG Copper Wire

Estimated Voltage Drop: 15.24% · Max Recommended Fuse/Breaker: 125A

Adjust the Numbers

Instant Answer

Use 4/0 AWG Copper Wire

Estimated Voltage Drop: 15.24% · Limit: 2%

Recommended AWG4/0 AWG Copper
Circular Mils (CM)211,600
Voltage Lost1.83 V
Percent Drop15.24%
Power Lost182.9 W
Conductor Ampacity (75°C)230 A
Max Recommended Fuse/Breaker125 A

Based on NEC Table 310.16 (75°C ampacity) and Chapter 9, Table 8 (circular mils). Assumes a 30°C (86°F) ambient, ≤3 current-carrying conductors. Always verify against your local jurisdiction's current NEC/CEC adoption before installation.

Full Technical Spec Table

AWG Circular Mils Ampacity (75°C) Voltage Lost % Drop Power Lost Max Fuse
14 AWG 4,110 20A 94.16V 784.67% 9416.1W 20A
12 AWG 6,530 25A 59.26V 493.87% 5926.5W 25A
10 AWG 10,380 35A 37.28V 310.69% 3728.3W 35A
8 AWG 16,510 50A 23.44V 195.34% 2344.0W 50A
6 AWG 26,240 65A 14.75V 122.90% 1474.8W 60A
4 AWG 41,740 85A 9.27V 77.26% 927.2W 80A
2 AWG 66,360 115A 5.83V 48.60% 583.2W 110A
1/0 AWG 105,600 150A 3.66V 30.54% 366.5W 125A
2/0 AWG 133,100 175A 2.91V 24.23% 290.8W 125A
3/0 AWG 167,800 200A 2.31V 19.22% 230.6W 125A
4/0 AWG 211,600 230A 1.83V 15.24% 182.9W 125A

NEC Guidance for 100A Circuits at 12V

Under NEC Table 310.16, conductor ampacity is rated by insulation temperature class and ambient conditions. For a 100A load, the 75°C column is the standard reference used by most residential and commercial terminations, since the vast majority of circuit breakers and equipment terminals are only rated for 60°C or 75°C. At 12V, voltage drop becomes a more significant design constraint because low-voltage DC and solar systems are far more sensitive to line losses.

This calculation assumes a 46m one-way run, which is doubled in the voltage drop formula to account for both the outgoing and return conductors. The NEC recommends keeping voltage drop under 3% for branch circuits and under 5% combined for feeders and branch circuits together, though solar and off-grid DC installers typically target a stricter 2% limit to preserve panel output efficiency.

Ambient temperature also affects the usable ampacity of a conductor. Table 310.15(B)(1) derating factors reduce the rated ampacity as ambient temperature rises above 30°C (86°F):

For installations in attics, near rooftops, or in high-heat industrial environments, always apply the appropriate derating factor before finalizing wire gauge, and consult a licensed electrician for any circuit exceeding 60A or involving service entrance conductors. This tool provides an engineering estimate only and does not replace a code-compliant load calculation performed by a qualified professional.